Project Description
Tyre Plant
TYPE OF INDUSTRY – Tyre Plant at Dhaka, Bangladesh
YEAR OF IMPLEMENTATION – 2015
PROBLEMS
- Not possible to operate Plant at Full load on Captive Plant (Gas Generator)
- Frequent Electrical breakdowns
OBSERVATIONS
After conducting Power Quality Audit in the plant, following observations are made:
Total Harmonic Distortion (THD) current is 41.20 %.
THD voltage is 24.70 %.
Power factor is 0.46
The high Harmonics current generated by DC drive motor 1500 KW at 660 V Bus, result to very high Voltage Harmonics Distortion due to high impedance of Generators. Due to this , the Generators were hunting during operation and not able to operate DC drive motor at full load.
SOLUTION
-
Detune Resonance condition by providing suitable Automatic Passive Harmonic Filter Banks.
-
Add Digitally controlled Active Harmonic Filter Bank to control THDI & THDV < 5% as per IEEE 519-1992
System Improvement Post Implementation
Measurement at main incomer ACB.
Sr No. | Parameters | Before Installation of Harmonic Filter banks | After Installation of Harmonic Filter bank |
---|---|---|---|
1. | Fundamental current I1 Amp | 1426 A | 1384 |
2. | — | — | — |
3. | 3rd Harmonic Current I3 | 158 | 34A |
4. | 5th Harmonic Current I5 | 440 A | 127A |
5. | 7th Harmonic Current I7 | 68 A | 8 A |
6. | 11th Harmonic Current I11 | 118 A | 76 A |
7. | 13th Harmonic Current I13 | 70 A | 3 A |
8. | Total Harmonic Distortion Current % | 41.20% | 10% |
9. | Total Harmonic Distortion Voltage % | 24.70 % | 9 % |
10. | Cos Ø | 0.72 | 0.80 lag |
11. | True Power Factor PF | 0.46 | 0.79 lag |
12. | True RMS current Amp | 1448 A | 1391 A |
13. | True RMS Voltage V/ Phase | 358 V | 366 V |
RESULT
-
THDI & THDV reduced to < 10% from initial value of 41% & 25% respectively after Installation of Harmonic Filters.
-
100% loading on Captive Generation is possible after installation of Harmonic Filter Banks.
-
Huge Saving in Energy Charges due to fully operation of plant on Gas Generation.