Project Description
Pharmaceutical Industry
TYPE OF INDUSTRY – Pharmaceutical Industry, Himachal Pradesh, India
YEAR OF IMPLEMENTATION – 2016
PROBLEMS
- High Harmonic Distortion
- Low power factor
- High KVAH consumption
- Frequent breakdown in VFDs
OBSERVATIONS
After conducting Power Quality Audit in the plant, following observations are made:
5th & 7th Harmonics are getting amplify due to resonance effects between conventional type APFC (w/o Harmonic Filters) & Transformer impedance.
The Amplification of Harmonics cause frequent failure in VFDs drives.
SOLUTION
-
Detune Resonance condition by providing suitable Passive Harmonic Filter Banks.
-
Add Digitally controlled Active Harmonic Filter Bank to control THDI & THDV < 5% as per IEEE 519-1992
Project Implementation
Design, Manufacturing & Installation of Hybrid Harmonic Filter Banks -Automatic Passive Harmonic filter bank 1500 kvar and Digitally controlled Active Harmonic filter banks of 150A, 3ph,4 wire at main incomer.
System Improvement Post Implementation
Measurement at main incomer — Supply
Sr No. | Parameters | Before Installation of Harmonic Filter banks | After Installation of Harmonic Filter bank |
---|---|---|---|
1. | Fundamental current I1 Amp | 1736 A | 1462 A |
2. | 3nd Harmonic Current I2 | 50.1 A | 53 A |
3. | 5rd Harmonic Current I3 | 135.4 A | 57A |
4. | 7th Harmonic Current I5 | 58.3 A | 34 A |
5. | 11th Harmonic Current I7 | 18.8 A | 15 A |
6. | 13th Harmonic Current I11 | 12.1 A | 9 A |
7. | Total Harmonic Distortion Current % | 9.48 | 5.8 |
8. | Total Harmonic Distortion Voltage % | 2.8 | 2.3 |
9. | Cos Ø | 0.94 | 1 |
10. | True Power Factor PF | 0.95 | 1 |
11. | True RMS current Amp | 1823 | 1462 |
12. | True RMS Voltage V/ Phase | 227.6 | 230 |
13. | Total KW | 1135 | 1105 |
14. | Total KVA | 1172 | 1107 |
RESULT
-
THDI & THDV reduced to < 5%.
-
The 5th & 7th Harmonics current are reduced.
-
PF improvement to unity (1.0) from 0.94 lag
-
Apprx 6 % saving in KVA.
-
Reduction in Electrical Breakdown in the Plant.