Project Description
Paper Industry
TYPE OF INDUSTRY – Paper Industry Tamilnadu, India
YEAR OF IMPLEMENTATION – 2016
PROBLEMS
- Total Harmonic Distortion more than TNERC requirement.
OBSERVATIONS
After conducting Power quality Audit in the plant following observations are made.
Total Harmonic Distortion (THD) current is 17.50 %.
THD voltage is 5.30 % .
Power factor is 0.976
The 3rd ,5th , 7th and 11th Harmonics are predominant.
SOLUTION
Digitally controlled Active Harmonic Filter Bank to control THDI & THDV.
System Improvement Post Implementation
Measurement at main incomer 33 KV at PCC
Sr No. | Parameters | Before Installation of Harmonic Filter banks | After Installation of Harmonic Filter bank |
---|---|---|---|
1. | Fundamental current I1 Amp | 13.05 A | 13.0 A |
2. | 2nd Harmonic Current I2 | — | — |
3. | 3rd Harmonic Current I3 | 0.17 A | 0.23 A |
4. | 5th Harmonic Current I5 | 1.83 A | 0.09 A |
5. | 7th Harmonic Current I7 | 1.0 A | 0.12 A |
6. | 11th Harmonic Current I11 | 0.63 A | 0.14 A |
7. | 13th Harmonic Current I13 | — | 24 A |
8. | Total Harmonic Distortion Current % | 17.50 % | 2.5 % |
9. | Total Harmonic Distortion Voltage % | 5.30 % | 2.1 % |
10. | Cos Ø | 0.986 | 0.999 lag |
11. | True Power Factor PF | 0.976 | 0.996 lag |
12. | True RMS current Amp | 14.4 A | 13.20 A |
13. | True RMS Voltage V/ Phase | 20.30 kv | 20.31 V |
RESULT
-
THDI & THDV reduced to < 2.5 % & 2.1 % from initial value of 17.50 % & 5.3 % respectively after Installation of Harmonic Filters.
-
Power Factor Improved to 0.996 .
-
Plant Comply with Tamil Nadu Electricity and Regulatory Commission (TNERC) requirement of Harmonic Distortion and Saved 15 % monthly penalty.